• View products by industry:

Averaging RTDs Page

  
HVAC RTDs - Averaging
Temperature Limits Moderate (M) Range RTDs
-50 to 250 °C (-58 to 482 °F)
Element Resistance 100 Ohms at 0 °C with tolerances of :
Class A +/-.06% @ 0°C
Class B +/-.12% @ 0°C
Class C +/-.5% @ 0°C
Temperature Coefficient .0038500 Nominal Temperature Coefficient
Class A: Change in T = +/-(.15°C + 002|t|)
Class B: Change in T = +/-(.30°C + 005|t|)
Class A: Change in T = +/-(1.3°C + 005|t|)
Time Constant Six seconds maximum for 63.2% response to change in temperature per ASTM E644
Repeatability Less than +/-.06% change in ice point resistance after 10 consecutive cycles between ice point and 250 °C
Long Term Stability Less than +/- .02% ice point resistance shift after 1000 hours at 250 °C
Self Heating 10 mW/°C in water moving at 3 feet/sec.
Hysteresis +/-.15% of Span Temperature

   Class 510 Bendable General Purpose
Configure
   Used to detect "average" temperatures in systems where point measurements are inadequate.
   Class 511 1/2 X 1/2 NPT Adj Compression Fitting
Configure
   Used to detect "average" temperatures in systems where point measurements are inadequate.
   Class 512 Welded Twin Thd Hex Fitting
Configure
   Used to detect "average" temperatures in systems where point measurements are inadequate.
   Class 513 Welded Process Thd Hex Fitting
Configure
   Used to detect "average" temperatures in systems where point measurements are inadequate.
   Class 514 Conduit Box
Configure